عنوان
|
Precise Calculation of Dead Time in High Voltage Transmission Lines Using Network Equivalencing Method in Time Domain
|
نوع پژوهش
|
مقاله ارائه شده کنفرانسی
|
کلیدواژهها
|
Power Transmission Lines, Single Phase, Auto reclosure, dead Time, EMTP-ATP
|
چکیده
|
Various studies have showed that about 70 to 90% of single line to ground faults occurred on High voltage transmission lines have transient nature. This type of faults is cleared by temporary outage (by the single phase auto-reclosure). The interval between opening and reclosing of the faulted phase circuit breakers is named "Dead Time" that is varying about several hundred milliseconds. For adjustment of traditional single phase auto-reclosures that usually are not intelligent, it is necessary to calculate the dead time in the off-line condition precisely. If the dead time used in adjustment of single phase auto-reclosure is less than the real dead time, the reclosing of circuit breakers threats the power systems seriously. So in this paper a novel approach for precise calculation of dead time in power transmission lines based on the network equivalencing in time domain is presented. This approach has extremely higher precision in comparison with the traditional method based on Thevenin equivalent circuit. For comparison between the proposed approach in this paper and the traditional method, a comprehensive simulation by EMTPATP is performed on an extensive power network.
|
پژوهشگران
|
جمال مشتاق (نفر اول)، لاله اسلامی (نفر سوم)، محسن جنتی (نفر دوم)
|