مشخصات پژوهش

صفحه نخست /A Novel Application of ...
عنوان A Novel Application of Network Equivalencing Method in Time Domain To Precise Calculation Dead Time in Power Transmission Line
نوع پژوهش مقاله چاپ‌شده در مجلات علمی
کلیدواژه‌ها Dead Time; Network Equivalencing; High Voltage transmission Lines; Single Phase Auto -Reclosure;
چکیده ( Regarding the findings of diverse studies on high voltage transmission lines, about 90 % of single-line-to-ground occurring faults are inherently transient. These faults are cleared by temporary outage (or by the single phase auto-reclosure). The interval between opening and reclosing of the faulted phase circuit breakers is named “Dead Time” that varies about several hundred milliseconds. In order to adjust traditional single-phase auto-reclosures that usually are not intelligent, it is necessary to calculate the dead time in the off-line condition precisely. If the dead time used in adjusting single phase auto-reclosure is less than the real dead time, the reclosing of circuit breakers threats the power systems seriously. So in this paper a novel approach for precise calculation of dead time in power transmission lines based on the network equivalencing in time domain is presented. This approach has extremely higher precision compared with the traditional method based on Thevenin equivalent circuit. For comparison between the proposed approach in this paper and the traditional method, a comprehensive simulation by EMTP-ATP is performed on an extensive power network.
پژوهشگران لاله اسلامی (نفر دوم)، جمال مشتاق (نفر اول)